What is the the max voltage and max current SPF Dry Contact can manage?

Max voltage and current: 250VAC/3A


Wire size of PV, battery and AC

8AWG for PV, is the The maximum allowed wire size for PV cable is 8AWG.

8AWG for Battery, is the The maximum allowed wire size for battery cable is 8AWG.

4AWG for AC, is the The maximum allowed wire size for AC able is 4AWG.




What is the maximum allowable voltage and current?

Maximum allow up to 550V and 13.5A.  Any voltage and current exceed the limit would cause the inverter to shut down or damage.


What voltage values to adjust if encountered AC High or Low outrange error?

High voltage

53 - changed to 5600

57 - 5871

61 – 5871

65 – changed to 5600

80 - changed to 5600

Low voltage

52 – 3838 - changed to 3400

56 - 1905

60 - 1905

64 – 385.8 - changed to 3400

Datalogger showed Online but Inverter showed Offline (WiFi-F, -S, -X)

a. Reset the datalogger

b. Update the datalogger firmware to the latest version

c. Uninstall the datalogger and reinsert it to make sure the USB port was fully connected

d. Blue light in blinking = Good communication between the datalogger and server 


How does the inverter maintain the operating temperature if I decide to lock the inverter in the enc

All the inverters came with natural ventilation method that exchange hot and cold air between the case surface.  NOT recommend, but if insist, need to have a good ventilation within the enclosure


How does the PVRSS Emergency Stop Switch function?

The emergency stop is used for stopping the XH-US system by manual, and also used for stopping the power supply to the transmitter of the RSD. Once installed and the button is pressed, this normally closed emergency button will open and cause the integrated transmitter to stop signaling the RSD devices which will cause the PV panels to stop operating and prevent DC flow into the inverter. When the emergency button is reset back to its normally closed position, this will cause the transmitter to begin its normal operations and signal the RSD to turn back on and allow PV energy to flow into the inverter again. 

How do I extend and obtain to the 15/20 years warranty status? The procedure is as below:

a. Customer submits the extension application in Growatt OSS system with the correct customer info and the product info;

b. Growatt reviews the request and fill in the extension price, then return back to the customer for payment with an email reminder;

c. Customer uploads the bank slip to Growatt OSS system for payment;

d. After payment confirmed and the extension card will be issued online;

Customer downloads the warranty extension card from the website and keep it for your record


Function and connection method of double meter of energy storage machine.

The user can connect the double meter to the energy storage machine according to the usage requirements to monitor the power of the inverter and the energy storage machine respectively. The specific setting is to set "Mode change➡Sensor➡Meter" through the LCD, one meter is connected to the "CT1/METER1" port, and the other meter is connected to the "485-1" or "485-2" port.

Why does the energy storage machine display “ Over Load!”?

Analysis:

    The energy storage machines under different MODELs have their output power upper limit, and this fault occurs when the machine output is overloaded.

Solution:

    Check whether the load of the energy storage machine exceeds the upper limit, and reduce the load to the rated range of the machine to solve the problem.

What is the the max voltage and max current SPF Dry Contact can manage?

Max voltage and current: 250VAC/3A


Wire size of PV, battery and AC

8AWG for PV, is the The maximum allowed wire size for PV cable is 8AWG.

8AWG for Battery, is the The maximum allowed wire size for battery cable is 8AWG.

4AWG for AC, is the The maximum allowed wire size for AC able is 4AWG.




What is the maximum allowable voltage and current?

Maximum allow up to 550V and 13.5A.  Any voltage and current exceed the limit would cause the inverter to shut down or damage.


What voltage values to adjust if encountered AC High or Low outrange error?

High voltage

53 - changed to 5600

57 - 5871

61 – 5871

65 – changed to 5600

80 - changed to 5600

Low voltage

52 – 3838 - changed to 3400

56 - 1905

60 - 1905

64 – 385.8 - changed to 3400

Datalogger showed Online but Inverter showed Offline (WiFi-F, -S, -X)

a. Reset the datalogger

b. Update the datalogger firmware to the latest version

c. Uninstall the datalogger and reinsert it to make sure the USB port was fully connected

d. Blue light in blinking = Good communication between the datalogger and server 


How does the inverter maintain the operating temperature if I decide to lock the inverter in the enc

All the inverters came with natural ventilation method that exchange hot and cold air between the case surface.  NOT recommend, but if insist, need to have a good ventilation within the enclosure


How does the PVRSS Emergency Stop Switch function?

The emergency stop is used for stopping the XH-US system by manual, and also used for stopping the power supply to the transmitter of the RSD. Once installed and the button is pressed, this normally closed emergency button will open and cause the integrated transmitter to stop signaling the RSD devices which will cause the PV panels to stop operating and prevent DC flow into the inverter. When the emergency button is reset back to its normally closed position, this will cause the transmitter to begin its normal operations and signal the RSD to turn back on and allow PV energy to flow into the inverter again. 

How do I extend and obtain to the 15/20 years warranty status? The procedure is as below:

a. Customer submits the extension application in Growatt OSS system with the correct customer info and the product info;

b. Growatt reviews the request and fill in the extension price, then return back to the customer for payment with an email reminder;

c. Customer uploads the bank slip to Growatt OSS system for payment;

d. After payment confirmed and the extension card will be issued online;

Customer downloads the warranty extension card from the website and keep it for your record


Function and connection method of double meter of energy storage machine.

The user can connect the double meter to the energy storage machine according to the usage requirements to monitor the power of the inverter and the energy storage machine respectively. The specific setting is to set "Mode change➡Sensor➡Meter" through the LCD, one meter is connected to the "CT1/METER1" port, and the other meter is connected to the "485-1" or "485-2" port.

Why does the energy storage machine display “ Over Load!”?

Analysis:

    The energy storage machines under different MODELs have their output power upper limit, and this fault occurs when the machine output is overloaded.

Solution:

    Check whether the load of the energy storage machine exceeds the upper limit, and reduce the load to the rated range of the machine to solve the problem.

What is the the max voltage and max current SPF Dry Contact can manage?

Max voltage and current: 250VAC/3A


Wire size of PV, battery and AC

8AWG for PV, is the The maximum allowed wire size for PV cable is 8AWG.

8AWG for Battery, is the The maximum allowed wire size for battery cable is 8AWG.

4AWG for AC, is the The maximum allowed wire size for AC able is 4AWG.




What is the maximum allowable voltage and current?

Maximum allow up to 550V and 13.5A.  Any voltage and current exceed the limit would cause the inverter to shut down or damage.


What voltage values to adjust if encountered AC High or Low outrange error?

High voltage

53 - changed to 5600

57 - 5871

61 – 5871

65 – changed to 5600

80 - changed to 5600

Low voltage

52 – 3838 - changed to 3400

56 - 1905

60 - 1905

64 – 385.8 - changed to 3400

Datalogger showed Online but Inverter showed Offline (WiFi-F, -S, -X)

a. Reset the datalogger

b. Update the datalogger firmware to the latest version

c. Uninstall the datalogger and reinsert it to make sure the USB port was fully connected

d. Blue light in blinking = Good communication between the datalogger and server 


How does the inverter maintain the operating temperature if I decide to lock the inverter in the enc

All the inverters came with natural ventilation method that exchange hot and cold air between the case surface.  NOT recommend, but if insist, need to have a good ventilation within the enclosure


How does the PVRSS Emergency Stop Switch function?

The emergency stop is used for stopping the XH-US system by manual, and also used for stopping the power supply to the transmitter of the RSD. Once installed and the button is pressed, this normally closed emergency button will open and cause the integrated transmitter to stop signaling the RSD devices which will cause the PV panels to stop operating and prevent DC flow into the inverter. When the emergency button is reset back to its normally closed position, this will cause the transmitter to begin its normal operations and signal the RSD to turn back on and allow PV energy to flow into the inverter again. 

How do I extend and obtain to the 15/20 years warranty status? The procedure is as below:

a. Customer submits the extension application in Growatt OSS system with the correct customer info and the product info;

b. Growatt reviews the request and fill in the extension price, then return back to the customer for payment with an email reminder;

c. Customer uploads the bank slip to Growatt OSS system for payment;

d. After payment confirmed and the extension card will be issued online;

Customer downloads the warranty extension card from the website and keep it for your record


Function and connection method of double meter of energy storage machine.

The user can connect the double meter to the energy storage machine according to the usage requirements to monitor the power of the inverter and the energy storage machine respectively. The specific setting is to set "Mode change➡Sensor➡Meter" through the LCD, one meter is connected to the "CT1/METER1" port, and the other meter is connected to the "485-1" or "485-2" port.

Why does the energy storage machine display “ Over Load!”?

Analysis:

    The energy storage machines under different MODELs have their output power upper limit, and this fault occurs when the machine output is overloaded.

Solution:

    Check whether the load of the energy storage machine exceeds the upper limit, and reduce the load to the rated range of the machine to solve the problem.

What is the the max voltage and max current SPF Dry Contact can manage?

Max voltage and current: 250VAC/3A


Wire size of PV, battery and AC

8AWG for PV, is the The maximum allowed wire size for PV cable is 8AWG.

8AWG for Battery, is the The maximum allowed wire size for battery cable is 8AWG.

4AWG for AC, is the The maximum allowed wire size for AC able is 4AWG.




What is the maximum allowable voltage and current?

Maximum allow up to 550V and 13.5A.  Any voltage and current exceed the limit would cause the inverter to shut down or damage.


What voltage values to adjust if encountered AC High or Low outrange error?

High voltage

53 - changed to 5600

57 - 5871

61 – 5871

65 – changed to 5600

80 - changed to 5600

Low voltage

52 – 3838 - changed to 3400

56 - 1905

60 - 1905

64 – 385.8 - changed to 3400

Datalogger showed Online but Inverter showed Offline (WiFi-F, -S, -X)

a. Reset the datalogger

b. Update the datalogger firmware to the latest version

c. Uninstall the datalogger and reinsert it to make sure the USB port was fully connected

d. Blue light in blinking = Good communication between the datalogger and server 


How does the inverter maintain the operating temperature if I decide to lock the inverter in the enc

All the inverters came with natural ventilation method that exchange hot and cold air between the case surface.  NOT recommend, but if insist, need to have a good ventilation within the enclosure


How does the PVRSS Emergency Stop Switch function?

The emergency stop is used for stopping the XH-US system by manual, and also used for stopping the power supply to the transmitter of the RSD. Once installed and the button is pressed, this normally closed emergency button will open and cause the integrated transmitter to stop signaling the RSD devices which will cause the PV panels to stop operating and prevent DC flow into the inverter. When the emergency button is reset back to its normally closed position, this will cause the transmitter to begin its normal operations and signal the RSD to turn back on and allow PV energy to flow into the inverter again. 

How do I extend and obtain to the 15/20 years warranty status? The procedure is as below:

a. Customer submits the extension application in Growatt OSS system with the correct customer info and the product info;

b. Growatt reviews the request and fill in the extension price, then return back to the customer for payment with an email reminder;

c. Customer uploads the bank slip to Growatt OSS system for payment;

d. After payment confirmed and the extension card will be issued online;

Customer downloads the warranty extension card from the website and keep it for your record


Function and connection method of double meter of energy storage machine.

The user can connect the double meter to the energy storage machine according to the usage requirements to monitor the power of the inverter and the energy storage machine respectively. The specific setting is to set "Mode change➡Sensor➡Meter" through the LCD, one meter is connected to the "CT1/METER1" port, and the other meter is connected to the "485-1" or "485-2" port.

Why does the energy storage machine display “ Over Load!”?

Analysis:

    The energy storage machines under different MODELs have their output power upper limit, and this fault occurs when the machine output is overloaded.

Solution:

    Check whether the load of the energy storage machine exceeds the upper limit, and reduce the load to the rated range of the machine to solve the problem.

What is the the max voltage and max current SPF Dry Contact can manage?

Max voltage and current: 250VAC/3A


Wire size of PV, battery and AC

8AWG for PV, is the The maximum allowed wire size for PV cable is 8AWG.

8AWG for Battery, is the The maximum allowed wire size for battery cable is 8AWG.

4AWG for AC, is the The maximum allowed wire size for AC able is 4AWG.




What is the maximum allowable voltage and current?

Maximum allow up to 550V and 13.5A.  Any voltage and current exceed the limit would cause the inverter to shut down or damage.


What voltage values to adjust if encountered AC High or Low outrange error?

High voltage

53 - changed to 5600

57 - 5871

61 – 5871

65 – changed to 5600

80 - changed to 5600

Low voltage

52 – 3838 - changed to 3400

56 - 1905

60 - 1905

64 – 385.8 - changed to 3400

Datalogger showed Online but Inverter showed Offline (WiFi-F, -S, -X)

a. Reset the datalogger

b. Update the datalogger firmware to the latest version

c. Uninstall the datalogger and reinsert it to make sure the USB port was fully connected

d. Blue light in blinking = Good communication between the datalogger and server 


How does the inverter maintain the operating temperature if I decide to lock the inverter in the enc

All the inverters came with natural ventilation method that exchange hot and cold air between the case surface.  NOT recommend, but if insist, need to have a good ventilation within the enclosure


How does the PVRSS Emergency Stop Switch function?

The emergency stop is used for stopping the XH-US system by manual, and also used for stopping the power supply to the transmitter of the RSD. Once installed and the button is pressed, this normally closed emergency button will open and cause the integrated transmitter to stop signaling the RSD devices which will cause the PV panels to stop operating and prevent DC flow into the inverter. When the emergency button is reset back to its normally closed position, this will cause the transmitter to begin its normal operations and signal the RSD to turn back on and allow PV energy to flow into the inverter again. 

How do I extend and obtain to the 15/20 years warranty status? The procedure is as below:

a. Customer submits the extension application in Growatt OSS system with the correct customer info and the product info;

b. Growatt reviews the request and fill in the extension price, then return back to the customer for payment with an email reminder;

c. Customer uploads the bank slip to Growatt OSS system for payment;

d. After payment confirmed and the extension card will be issued online;

Customer downloads the warranty extension card from the website and keep it for your record


Function and connection method of double meter of energy storage machine.

The user can connect the double meter to the energy storage machine according to the usage requirements to monitor the power of the inverter and the energy storage machine respectively. The specific setting is to set "Mode change➡Sensor➡Meter" through the LCD, one meter is connected to the "CT1/METER1" port, and the other meter is connected to the "485-1" or "485-2" port.

Why does the energy storage machine display “ Over Load!”?

Analysis:

    The energy storage machines under different MODELs have their output power upper limit, and this fault occurs when the machine output is overloaded.

Solution:

    Check whether the load of the energy storage machine exceeds the upper limit, and reduce the load to the rated range of the machine to solve the problem.